8.5.1
Display status page
12.3
8.5.2
Display menu mode
"One level down" menu element
"Information" menu element
"Level up" menu element
"Selection/setting" menu element
±
8.5.3
Display error page
E000
42
Operation
The standard view on the display is the status page. The current setpoint is displayed in
the number segments. Other settings are displayed using symbols.
NOTICE
For twin-head pump operation, the status page additionally shows the operating
mode ("parallel operation" or "main/reserve") in the form of symbols. The display of
the slave pump shows "SL".
The electronic module functions can be accessed via the menu structure. The menu
contains sub-menus on several levels. A number is assigned to each menu and sub-
menu.
The menu elements "Level up" or "Level down" are used to change the menu levels, e.g.
from menu <4.1.0.0> to <4.1.1.0>.
The currently selected menu element is identified by the menu number on the display
and the associated symbol.
Select menu numbers within a menu level sequentially by turning the operating button.
NOTICE
If the operating button is not operated for 30 seconds in menu mode, the display re-
turns to the status page. In this case, no change is accepted.
Every menu level can contain four different element types:
If the "Level down" arrow appears in the display, pressing the operating button
switches to the next level down. After the change, the number of the new menu level
increases by one digit (e.g. from menu <4.1.0.0> to menu <4.1.1.0>).
When this symbol appears, current settings or measurements cannot be changed
(standard symbol for "Access disable"). The displayed information is read-only.
When the "Level up" arrow appears in the display, pressing the operating button briefly
switches to the next highest menu level (e.g. from menu <4.1.5.0> to menu <4.1.0.0>).
NOTICE
If the operating button is pressed for 2 seconds while the "Level up" arrow appears
in the display, the display returns to the status display.
The "Selection/setting" symbol opposite does not appear in the display. The symbol in-
dicates menu items in these instructions that allow selection or adjustment.
If a "Selection/setting" menu element is selected, pressing the operating button will
change to edit mode.
In edit mode, the adjustable value flashes. Turning the operating button changes the
value, pressing it again saves the value that has been set.
In some menus, after pressing the operating button, acceptance of the input will be
confirmed by a brief display of the "OK" symbol.
If an error occurs, the display changes from the status page to the error page. The dis-
play shows the letter "E" and the three-digit error code, separated by a decimal point.