Wilo Yonos GIGA-N 80 Installation And Operating Instructions Manual page 33

Table of Contents

Advertisement

6.7.5
Terminal assignment
1.5 ... 4 kW:
M16
M12
SSM
SBM
Fig. 30: Threaded cable glands
Designation
Assignment
Mains connection voltage
L1, L2, L3
Protective earth conductor connec-
; (PE)
tion
Actual value input
In1
(1) (input)
Setpoint input
In2 (input)
Earth connections
GND (2)
DC voltage for an external con-
+ 24 V
sumer/signal transmitter
(3) (output)
External pump cycling
AUX
Multi Pump
MP
"Overriding OFF" control input for
external, potential-free switch
Ext. Off
Installation and operating instructions Wilo-Yonos GIGA-N
Installation and electrical connection
Earth terminals
Table 12: Tightening torques for control, power and earth terminals
5.5 ... 7.5 kW:
M25
M12
M12
M16
M20
M16
M20
M25
Notes
3~380 V AC – 3~440 V AC, 50/60 Hz, IEC 38
Type of signal: Voltage (0-10 V, 2-10 V)
Input resistance: R
≥ 10 kΩ
i
Type of signal: Current (0-20 mA, 4-20 mA)
Input resistance: R
= 500 Ω
i
Can be configured in the service menu <5.3.0.0>
Connected at the factory via the M12 threaded cable gland, via In1 (1),
GND (2), + 24 V (3) according to the sensor cable designations (1, 2, 3).
In2 can be used as the input for remote adjustment of the setpoint in any
operating mode.
Type of signal: Voltage (0-10 V, 2-10 V) Input resistance: R
Type of signal: Current (0-20 mA, 4-20 mA) Input resistance: R
Can be configured in the service menu <5.4.0.0>
For both input In1 and In2
Max. load: 60 mA
The voltage is short-circuit proof.
Contact load: 24 V DC/10 mA
Pump cycling can be performed using an external, potential-free contact.
If external pump cycling has been previously activated, bridging the two
terminals once executes a pump cycling operation. Bridging them a second
time will cause the procedure to repeat, provided the minimum run time is
adhered to.
Can be configured in the service menu <5.1.3.2> Contact load:
24 V DC/10 mA
Interface for twin-head pump function
The pump can be switched on/off via the external potential-free contact.
Systems with a high switching frequency (> 20 on/off operations per day)
should be switched on/off via "External off".
Can be configured in the service menu <5.1.7.0> Contact load:
24 V DC/10 mA
Tightening torque
[Nm] ± 10 %
0.5
11 ... 22 kW:
M16 M12
≥ 10 kΩ
i
en
M20 M40
= 500 Ω
i
33