Mounting and wiring
3.6
KL4034 - connection and LED description
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
Fig. 12: KL4034 - connection and LEDs
KL4034 connection
Terminal point
No.
Output1
1
GND
2
Output3
3
GND
4
Output2
5
GND
6
Output4
7
GND
8
LED description KL4034
LED
Color
LED Run1
green
LED Run2
LED Run3
LED Run4
24
WARNING
Comment
+ Output 1
Internal ground (internally connected to terminal point 6)
+ Output 3
Internal ground (internally connected to terminal point 8)
+ Output 2
Internal ground (internally connected to terminal point 2)
+ Output 4
Internal ground (internally connected to terminal point 4)
Description
On:
Normal operation
Off:
Watchdog timer overflow has occurred. If no process data is transmitted to the bus cou-
pler for 100 ms, the green LEDs go out. The output assumes a user-specified voltage
(see Feature register [} 38]).
Version: 4.1