Beckhoff KL403 Series Documentation page 44

Single-, dual- and four-channel analog output terminals, signal range: -10 v to +10 v
Table of Contents

Advertisement

Access from the user program
• The terminal returns the value of the control byte as a receipt in the status byte.
• The terminal returns the current value of the feature register in the input data word (byte 1 and byte 2).
V. Write Register 31 (reset code word)
Output Data
Byte 0: Control byte
0xDF (1101 1111
)
bin
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 set means: writing to the register.
• Bits 0.5 to 0.0 specify the register number 31 with 01 1111
• The output data word (byte 1 and byte 2) contains 0x0000 for reactivating write protection.
Input Data (answer of the bus terminal)
Byte 0: Status byte
0x9F (1001 1111
)
bin
Explanation:
• The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of
the control byte.
• The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still
displayed are invalid!
44
Byte 1: DataOUT1, high byte
0x00
Byte 1: DataIN1, high byte
0xXX
Version: 4.1
Byte 2: DataOUT1, low byte
0x00
.
bin
Byte 2: DataIN1, low byte
0xXX
KL403x