5. Commissioning
1
4
0,5K
1
2
3
86
n CIRC. CURVE ...
Heating curve circuit A, B or C
Outside temperature (°C)
x
Water flow temperature (°C)
y
Maximum temperature of the circuit B - C
A
M001678-B
n ANTICIP.A, ANTICIP.B, ANTICIP.C
Room temperature instruction - Comfort
A
Room temperature instruction - Low
Z
Time schedule
E
Anticipation time = Accelerated reheating phase
R
The anticipation function calculates the heating restart time to reach
the desired room temperature less 0.5 K at the time programmed for
switching to comfort mode.
The start time of the timed programmed corresponds to the end of the
accelerated reheating phase.
The function is activated by setting a different OFF value.
The value set corresponds to the time considered necessary to return
the installation to the required temperature (outside temperature
8801N033
0°C), starting from a residual room temperature corresponding to the
low nocturnal instruction.
Anticipation is optimised if a room sensor is connected.
The regulator will automatically fine set the anticipation time.
This function is dependent on the surplus output available
in the installation.
n SCREED DRYING
Used to force a constant flow temperature or a train to accelerate
screed drying on underfloor heating.
The setting for these temperatures must follow the screed-layer's
recommendations.
The activation of this parameter (setting other than OFF) forces the
permanent display of SCREED DRYING and deactivates all other
functions on the control unit.
When floor drying is active on a circuit, all other circuits (e.g. DHW)
are shut down. The use of this function is only possible on circuits B
and C.
MCA 35
15/06/12 - 300022160-001-01