Basic Setting For The Gas/Air Ratio; Checks And Adjustments After Commissioning; Displaying The Parameters In Extended Mode - DeDietrich Innovens MCA 35 Installation And Service Manual

Wall-hung gas condensing boilers
Hide thumbs Also See for Innovens MCA 35:
Table of Contents

Advertisement

MCA 35
8
A
B
9
10
5.5

Checks and adjustments after commissioning

0
2
4
6
8
E
1
TEMP.: 68°
2
1
D
2
#
F
% $
AUTO
J
I
5"
Installer level - Menu #SYSTEM
Parameter
Adjustment range Description
INSTALLATION CLASSIC
EXTENDED
15/06/12 - 300022160-001-01
T001985-B
10
12
14
16
18
20
22
24
SUNDAY 11:45
!

:
<
STD
C002235-F-04
Displays the parameters of a conventional
installation
Displays all parameters
5.4.4.

Basic setting for the gas/air ratio

If the gas/air ratio is out of adjustment, the gas valve unit has a basic
setting. To do this, proceed as follows:
1. Switch off the boiler electrical power supply.
2. Close the gas valve on the boiler.
3. Remove the air inlet flue on the venturi.
4. Unscrew the top connection on the gas valve unit.
5. Disconnect the connector located under the fan.
6. Release the 2 clips holding the fan/mixing elbow unit in place on
the heat exchanger.
7. Completely remove the fan/mixing elbow unit.
¼ For steps 3 to 7 inclusive, see chapter: "Checking the burner
and cleaning the heat exchanger", page 99
8. Turn the setting screw A on the gas valve unit to modify the
position of the restrictor.
9. Turn the setting screw B on the gas valve unit anticlockwise until
it matches the front panel.
10.Turn the setting screw B on the gas valve unit by 6 turns clockwise.
11.Follow the procedure in reverse to re-assemble all of the
components.
5.5.1.
Displaying the parameters in extended
mode
The display mode on the control panel is set as standard in such a
way as only to show the conventional parameters. It is possible to
switch to extended mode by proceeding as follows:
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #SYSTEM.
Turn the rotary button to scroll through the menus or
4
modify a value.
Press the rotary button to access the selected menu
4
or confirm a value modification.
¼ For a detailed explanation of menu browsing, refer
to the chapter: "Browsing in the menus", page 62
3. Set parameter INSTALLATION to EXTENDED.
5. Commissioning
Factory setting Customer setting