DeDietrich Innovens MCA 35 Installation And Service Manual page 82

Wall-hung gas condensing boilers
Hide thumbs Also See for Innovens MCA 35:
Table of Contents

Advertisement

5. Commissioning
User level - Menu #SETTING
Parameter
Adjustment range Description
15 to 30 °C
SUM/WIN
NO
CALIBR. OUT
CALIBR. ROOM A
(1)(2)
(1)
-5.0 to +5.0 °C
OFFSET ROOM A
(3)
0.5 to 20 °C
ANTIFR. ROOM A
CALIBR. ROOM B
(2)(1)(4)
-5.0 to +5.0 °C
(3)
OFFSET ROOM B
(4)(1)
(4)
0.5 to 20 °C
ANTIFR. ROOM B
CALIBR. ROOM C
(4)(1)(2)
-5.0 to +5.0 °C
(4)
OFFSET ROOM C
(1)(3)
0.5 to 20 °C
(4)
ANTIFR. ROOM C
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
(2) The parameter is only displayed if a room sensor is connected to the circuit concerned
(3) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence
(4) The parameter is only displayed if the circuit concerned is actually connected
80
Used to set the outside temperature above
which heating will be shut down.
The heating pumps are shut down.
4
The burner will only start for domestic
4
hot water needs.
The symbol p appears.
4
Heating is never shut down automatically
Outside sensor calibration: Used to
correct the outside temperature
Calibration of the room sensor on
circuit A
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room offset on circuit A: Is used to set a
room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room temperature antifreeze activation
on circuit A
Calibration of the room sensor on
circuit B
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room offset on circuit B: Is used to set a
room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room temperature at which the antifreeze
mode is activated on circuit B
Calibration of the room sensor on
circuit C
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room offset on circuit C: Is used to set a
room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room temperature antifreeze activation
on circuit C
Factory setting
Customer
setting
22 °C
Outside temperature
Room temperature
of circuit A
0.0
6 °C
Room temperature
of circuit B
0.0
6 °C
Room temperature
of circuit C
0.0
6 °C
15/06/12 - 300022160-001-01
MCA 35