INNOVENS PRO MCA 160
Product evolution
JS
1. Purpose
MCA 160 boilers equipped with a DIEMATIC EVOLUTION or INICONTROL2 control panel, evolve:
Evolution of the DIEMATIC Evolution HMI : the new display is blue : better readability and quick access
-
icons.
-
The following electronic boards (PCB's) are evolving, to optimize the cascade operation and the
management of domestic hot water:
The SCB-10 PCB changes from version 0.5 to version 1.02.
The burner management PCB: CU-GH06 changes from software version 1.9 to 2.1 version.
Improved the siphon: easier removing and reassembly.
-
2. Compatibilities
In case of electronic card replacement, the compatibility of the software versions of the cards must be
checked, as indicated in the table below.
PCBs
CU-GH06 – v 1.9
7628632
CU-GH06 – v 2.1
7718238
Note: in blue, reference in spare parts (see point 4 hereafter).
CAUTION: In a cascade, the version of each card must be compatible with all other cards in the
cascade (all SCB-10 cards must be at the same version, as well as all CU-GH06 cards must be at the
same version).
QM
N° IT2683-en
SCB-10a
v 0.5
7636070
OK
-
1/4
SCB-10c
v 1.02
7718260
-
OK
EN
10/04/2019
IT2683-en

Advertisement

loading

Summary of Contents for DeDietrich INNOVENS PRO MCA 160

  • Page 1 Technical Information Wall-hung gas condensing boilers INNOVENS PRO MCA 160 Product evolution N° IT2683-en 10/04/2019 1. Purpose MCA 160 boilers equipped with a DIEMATIC EVOLUTION or INICONTROL2 control panel, evolve: Evolution of the DIEMATIC Evolution HMI : the new display is blue : better readability and quick access icons.
  • Page 2 3. Reading the software version To check the PCBs software version, check the label sticked on it, or access the Information menu. CU-GH06 PCB :  Version 1.9  SCB-10 PCB (DIEMATIC Evolution) : SCB-10 C Version 01.02 IT2683-en...
  • Page 3 On DIEMATIC Evolution control panel:  - Access the menus by pressing the key - Select and confirm the Information menu using the rotary button - Select menu CU-GH06 PCB - Select then validate parameter Software version to view the CU-GH06 version. - Press on key to get back - Select and confirm the SCB-10 PCB menu using the rotary button...
  • Page 4 4. Spare parts The versions of the SCB-10 and CU-GH06 cards must be compatible (see point 2 Compatibilities, or see indications below). In a cascade, all SCB-10 cards must be in the same version, as well as all CU- GH06 cards must be in the same version. Appliance Description Reference as spare part...