8. Troubleshooting
Code Faults
D07
SYST.SENS.FAIL.
D09
DHW S.FAILURE
D11
ROOM S.A FAIL.
D12
ROOM S.B FAIL.
D13
ROOM S.C FAIL.
D14
MC COM.FAIL
D15
ST.TANK S.FAIL
114
Cause
Description
of the
fault
SCU
System sensor fault
SCU
Domestic hot water sensor fault
Remarks:
Heating of domestic hot water
is no longer ensured.
The load pump operates.
The load temperature of the
dhw tank is the same as the
boiler.
SCU
A room temperature sensor
fault
B room temperature sensor
fault
C room temperature sensor
fault
Note:
The circuit concerned operates
without any influence from the
room sensor.
SCU
Communication failure
between the SCU PCB and the
boiler radio module
SCU
Storage tank sensor fault
Note:
The hot water storage tank
reheating operation is no longer
assured.
Checking / solution
Bad connection
Check whether the sensor is connected:
4
See chapter: "Deletion of sensors from the
memory in the PCB", page 116
Check the link and the connectors
4
Check that the sensor has been correctly fitted
4
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
Bad connection
Check whether the sensor is connected:
4
See chapter: "Deletion of sensors from the
memory in the PCB", page 116
Check the link and the connectors
4
Check that the sensor has been correctly fitted
4
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
Bad connection
Check whether the sensor is connected:
4
See chapter: "Deletion of sensors from the
memory in the PCB", page 116
Check the link and the connectors
4
Check that the sensor has been correctly fitted
4
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
Bad connection
Check the link and the connectors
4
Boiler module failure
Change the boiler module
4
Bad connection
Check whether the sensor is connected:
4
See chapter: "Deletion of sensors from the
memory in the PCB", page 116
Check the link and the connectors
4
Check that the sensor has been correctly fitted
4
Sensor fault
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
4
MCA 35
¼
¼
¼
¼
15/06/12 - 300022160-001-01