DeDietrich Innovens MCA 35 Installation And Service Manual page 85

Wall-hung gas condensing boilers
Hide thumbs Also See for Innovens MCA 35:
Table of Contents

Advertisement

MCA 35
Installer level - Menu #SECONDARY INSTAL.P
Parameter
(1)
BUILD. INERTIA
(2)
CIRC.CURVE A
(1)
ANTICIP.A
(1)
ROOM INFL. A
(2)
CIRC.CURVE B
(1)
ANTICIP.B
(1)
ROOM INFL. B
(2)
CIRC.CURVE C
(1)
ANTICIP.C
(1)
ROOM INFL. C
SCREED DRYING
(3)
START DRYING TEMP
(3)
STOP DRYING TEMP
(3)
NB DAYS DRYING
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f
(3) The parameter is only displayed if SCREED DRYING is other than OFF
(4) The parameter is only displayed if IN 0-10V is set to ON.
(5) The parameter is only displayed if P.DHW is set to PUMP
(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
(7) The parameter is only displayed if LEG PROTEC is other than OFF
15/06/12 - 300022160-001-01
Adjustment range
Description
0 (10 hours) to 10
Characterisation of building's inertia:
(50 hours)
0 for a building with low thermal inertia.
3 for a building with normal thermal
inertia.
10 for a building with high thermal inertia.
Modification of the factory setting is
only useful in exceptional cases.
0 to 4
Heating curve of the circuit A
¼ "CIRC. CURVE ...", page
86
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼ "ANTICIP.A, ANTICIP.B,
ANTICIP.C ", page 86
0 to 10
Influence of room sensor A
¼ "ROOM S.INFL", page 87
0 to 4
Heating curve of the circuit B
¼ "CIRC. CURVE ...", page
86
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼ "ANTICIP.A, ANTICIP.B,
ANTICIP.C ", page 86
0 to 10
Influence of room sensor B
¼ "ROOM S.INFL", page 87
0 to 4
Heating curve of the circuit C
¼ "CIRC. CURVE ...", page
86
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼ "ANTICIP.A, ANTICIP.B,
ANTICIP.C ", page 86
0 to 10
Influence of room sensor C
¼ "ROOM S.INFL", page 87
Drying the floor
NO, B, C, B+C
¼ "SCREED DRYING", page
86
20 to 50 °C
Screed drying start temperature
20 to 50 °C
Screed drying stop temperature
0 to 99
Number of days of floor drying
5. Commissioning
Factory
Customer
setting
setting
3 (22 hours)
1.5
NO
3
0.7
NO
3
0.7
NO
3
NO
20 °C
20 °C
0
83