6. CONNECTION TO THE CHIMNEY

For safety reasons the door of the appliances with constructive system 1, must be opened only for the
loading of the fuel or for removing the ashes, while during the operation and the rest, the door of the hearth
must remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open
door is allowed under supervision. The connection pipe to the flue must be the shortest possible, right, tight
and according to the current regulations.
The connection to the chimney must be performed with stable and strong pipes (we recommend a
thickness of 2 mm). The pipe for smokes exhaust must be fixed hermetically to the chimney. The diameter
10 m
(1)
from walls, pitches and trees. Otherwise raise it of at least 1 m
over the hindrance.
The chimney cap must exceed the ridge of the roof of at least
1 m.
>A
H min.
(1)ridge axis
α
Distance between the
roof ridge and the stack
A (m)
< 1,85 m
> 1,85 m
< 1,50 m
> 1,50 m
< 1,30 m
> 1,30 m
< 1,20 m
> 1,20 m
Instructions for installation, use and maintenance – EN – Rev.03
The chimney cap must not show hindrances within 10 m
> _ A
0,5 m
(2)roof
Minimum height of the stack
(measured from the outlet)
0,50 m above the roof ridge
1,00 m from the roof
0,50 m above the roof ridge
1,30 m from the roof
0,50 m above the roof ridge
2,00 m from the roof
0,50 m above the roof ridge
2,60 m from the roof
Figure 8
Figure 9
UNI 10683/98