  Creating an Local Area Network (LAN) Connection
To remove the Synergy Manager cover:
 1. Turn OFF the inverter ON/OFF/P switch, and wait until the green LED is blinking ,
indicating that the DC Voltage is safe (below 50V), or wait five minutes before
continuing to the next step.
 2. Turn OFF the inverter DC Disconnect Switch.
 3. Disconnect the AC to the inverter by turning OFF the circuit breakers on the
distribution panel.
 4. Release the six Allen screws of the cover and remove the Synergy Manager cover.
CAUTION!
When removing the cover, make sure not to damage internal components.
SolarEdge will not be held responsible for any components damaged as a
result of incautious cover removal.
ATTENTION!
Lors du retrait du couvercle, assurez-vous de ne pas endommager les
composants internes. SolarEdge ne peut être tenue pour responsable des
composants endommagés à la suite d'une imprudence dans le retrait du
couvercle.

Creating an Local Area Network (LAN) Connection

This communication option, enables connection to the SolarEdge monitoring platform
via Ethernet.
Ethernet cable specifications:
Cable type – a shielded Ethernet cable (CAT6) should be used
Maximum distance between the inverter and the router – 100 m/ 330 ft.
NOTE
If using an Ethernet cable longer than 10 m / 33 ft in areas where there is a
risk of induced Voltage surges by lightning, it is recommend to use external
surge protection devices. For details refer to:
Three Phase Inverter with Synergy Technology P/N: SExxK-xxxxIxxxx SExxK-xxxxIxxxx