NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on a
single Point of Common Connection. The default settings are in compliance with IEEE1547. Utility authorization is required
to change these set-points.
SolarEdge-Three Phase Inverter with Synergy Technology P/N: SExxK-xxxxIxxxx SExxK-xxxxIxxxx
Default Trip Limits and Times According to IEEE1547
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
V < 50%
50 % < V < 88%
110% < V < 120
V > 120 %
Frequency Range (Hz)
> 60.5
< 59.3 (Hawaii – 57)
0.16
2.00
1.00
0.16
Max. Clearing Time (Sec)
0.16
0.16
8 8
       