  Connecting Ground and AC to the Synergy Manager
WARNING!
To avoid shock hazard conditions, the PE wire must be connected to the
inverter before connecting the AC wires.
AVERTISSMENT!
Pour éviter les risques d'électrocution, le fil de terre doit être connecté à
l'onduleur avant de connecter les fils CA.
Use AC line wires with a maximum of 4/0 AWG cross section (For inverter models
SE50K to SE80K, use 3/0 AWG)
Use PE wire with a maximum 1/0 AWG cross section (For inverter models SE50K to
SE80K, use 3/0 AEG).
CAUTION!
Over-current protection for the AC output must be provided by the installer.
Connecting Protective Earth (PE)
WARNING!
Turn OFF the AC before connecting the AC terminals. When connecting
equipment Grounding wire, connect it before connecting the AC Line and
Neutral wires.
AVERTISSMENT!
Éteignez l'alimentation CA avant de connecter les bornes CA. Si vous souhaitez
relier le fil de mise à la terre de l'équipement, faites-le avant de connecter la
ligne CA et les fils du neutre.
To connect Protective Earth (PE) to the Synergy Manager:
1. Turn OFF and secure the main AC circuit breaker in OFF position at the circuit
breakers panel.
2.
Release the six Allen screws and carefully remove the cover of the Synergy Manager.
CAUTION!
When removing the cover, make sure not to damage internal components.
SolarEdge will not be held responsible for any components damaged as a
result of incautious cover removal.
ATTENTION!
Lors du retrait du couvercle, assurez-vous de ne pas endommager les
composants internes. SolarEdge ne peut être tenue pour responsable des
composants endommagés à la suite d'une imprudence dans le retrait du
couvercle.