IndraControl S20 Module With Safe Digital Outputs S20-PSDO-8/3
9.2.3

Parameterization errors

Code
Error cause
+ AddValue
0x2382
At least one output with
parameterized switch-off
+ 0x02F2
delay is still performing a
switch-off operation.
0x6320
The parameterization of
two related outputs does
+ 0x023X
not correspond to the
two-channel setting.
0x6320
The parameterized
switch-off delay time is
+ 0x02EX
outside the permissible
value range.
0x6320
For outputs parameter-
ized for two-channel op-
+ 0x029X
eration, the same settings
were not assigned for the
switch-off delay.
0x6320
Calculated and received
parameter data check-
+ 0x03F2
sums do not match.
0x6320
Wrong device type ID or
wrong module used
+ 0x03FB
Parameterization errors generate priority 1 diagnostic messages in the DiagState
object. These errors cannot be acknowledged. The parameterization must be
checked and corrected.
In order to determine what type of parameterization error has occurred, use the
software to access the controller online and read the error.
LED
Description/effect
FS
flash-
The module is kept in the safe state.
ing
Fig. 9-11
Parameterization errors (cannot be acknowledged)
Bosch Rexroth AG
Errors: messages and removal
Remedy
Wait until the switch-off operation is
complete and resend parameter
data to the module.
Correct value and resend parameter
data to the module.
Correct value and resend parameter
data to the module.
Correct value and resend parameter
data to the module.
Check checksums and resend pa-
rameter data to the module.
Check whether the correct module is
being used.
If you cannot resolve the problem,
please contact Bosch Rexroth.