IndraControl S20 Module With Safe Digital Outputs S20-PSDO-8/3
3.6

Local diagnostics and status indicators

Desig-
Color
nation
D
Red/
yellow/
green
UO
Green
FS
Red
P
Green
00-07
Green
00
01
D
Uo
10
11
FS
P
Fig. 3-3
Local diagnostics and status indicators
State
Description
Diagnostics for local bus communication
OFF
Devices are in the (power) reset state.
Flashing red
Device is operating, but is not connected to the previous device.
Red ON
The device is ready for operation, but has lost the connection to the bus head.
Yellow ON
The device is ready for operation, but has still not detected a valid cycle after
power-on.
Flashing
The device is not (yet) part of the active configuration.
yellow
Green/yellow
The device is ready for operation, communication within the station is OK.
alternating
Output data cannot be output and/or input data cannot be read.
There is a fault on the I/O side of the module.
Flashing green The device is ready for operation, communication within the station is OK.
The data is not valid. Valid data from the controller/higher-level network is not
available.
There is no fault in the module.
Green ON
The device is ready for operation, communication within the station is OK.
All data is valid. There are no faults.
Diagnostics for digital output supply
Green ON
Supply for the digital outputs is present and is > around 17 V DC.
Flashing green Supply for the digital outputs is not present or is < around 17 V DC.
Diagnostics for failure state
OFF
The safety application has valid F-Parameters and i-Parameters.
(Only applies if UO is on at the same time.)
Red ON
Hardware fault. Communication to the higher-level safe controller is disabled.
Flashing red
Module not parameterized or parameterization was not accepted.
Diagnostics for safe communication protocol
OFF
No safe communication
Green ON
Safe communication is running without errors.
Flashing green Safe communication is running. The controller is requesting "operator acknowl-
edgment".
Status of each output from 0 - 7
OFF
Output at logic "0"
Green ON
Output at logic "1"
02
03
04
05
06
07
12
13
14
15
16
17