DOK-CONTRL-S20*PSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-PSDO-8/3
Safe digital outputs
Output voltage
Simultaneity
Maximum switching frequency
Filter time
Switch-off delay for shutdown according to stop category 1
Maximum duration of the test pulses (when switched off;
active driving)
WARNING
The switch-on pulse can result in the loss of the safety function.
•
Please note that the load on a switch-on pulse (light test) of 1 ms must not fail or respond in a safety-critical way.
•
Please take this into consideration when selecting the actuator.
Maximum duration of the test pulses (when switched on)
WARNING
The switch-off pulse can result in the loss of the safety function.
•
Please note that the load on a switch-off pulse (dark test) of 3 ms must not fail or respond in a safety-critical way.
•
Please take this into consideration when selecting the actuator.
Status indicators
Diagnostics indicators
WARNING
Parasitic voltages can result in the loss of the safety function.
•
Connect the ground of the actuator to the ground terminal point of the corresponding output on the IndraControl S20 con
nector. An external ground may not be used.
•
The connected load must not respond in a hazardous way to test pulses.
Approvals
For the latest approvals, please visit www.boschrexroth.com/electrics.
U
100% up to 45°C (observe maximum current load)
1 Hz; 0.2 Hz at > 1 A
None
250 ms/500 ms/1 s/2 s/4 s/8 s/16 s/32 s/64 s/128 s
Accuracy: ±5% of the set value
See
1 ms
Loss of safety function
3 ms (depending on the load capacity)
Loss of safety function
One green LED per output
See
One red LED per output:
See
Loss of safety function
Bosch Rexroth AG
Technical data and ordering data
- 1 V, approximately
O
"Parameterization of the safe outputs" on page
"Local diagnostics and status indicators" on page
"Local diagnostics and status indicators" on page
61/82
30.
15.