Assembly, removal, and electrical installation
5.1.3
Setting the DIP switch
12-pos. DIP switch:
address
Overview of the
switch positions
MSB
LSB
Setting the address
IndraControl S20 Module With Safe Digital Outputs S20-PSDO-8/3
A DIP switch is located on the top of the module.
S1
11
10
Fig. 5-1
DIP switch
S1
Switch for setting the PROFIsafe address
Set the PROFIsafe address (F-Address) for the PROFIsafe device. PROFIsafe ad-
dresses up to 1023 (1
... 3FF
hex
11
10
9
8
Reserved
MSB
Fig. 5-2
Switch position for PROFIsafe
The most significant bit (MSB) has the highest value.
The least significant bit (LSB) has the lowest value.
•
Remove the marking field and set the address in the switch below it.
•
Reattach the marking field to the module.
The set address is only applied on power up. If the address is adjust-
ed during operation, the module responds with a failure state.
Positions 10 and 11 of the 12-pos. DIP switch are reserved for the
module operating mode and are preset by default. If a change is made
to the preset setting for positions 10 and 11, the module responds
with a failure state.
DOK-CONTRL-S20*PSDO*8*-AP02-EN-P
F-Address
off
on
9
7
5
3
1
8
6
4
2
0
) are permitted.
hex
PROFIsafe
Address switch
7
6
5
4
1
... 3FF
hex
hex
3
2
1
0
LSB