Behavior Of The Outputs In The Event Of Enabled Switch-Off Delay For Stop Category 1 - Bosch Rexroth IndraControl S20 Manual

Hide thumbs Also See for Rexroth IndraControl S20:
Table of Contents

Advertisement

DOK-CONTRL-S20*PSDO*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Outputs S20-PSDO-8/3
6.3
Behavior of the outputs in the event of enabled switch-off
delay for stop category 1
Switching off outputs
By the safe controller
After a bus error
After a short circuit, cross-circuit, failure
of the supply voltage or hardware fault
Fig. 6-2
Switching off of the outputs according to the trigger event and the parameterization
The time until the outputs are actually switched off depends on the parameteriza-
tion of the switch-off delay and the event that causes the outputs to be switched off.
Influence of set switch-off
delay
Yes
Yes
No
WARNING
Stop category 1 results in delayed switch-off.
Note the following for stop category 1:
The affected outputs are only set to the safe state once the switch-off
delay has elapsed.
In the event of an error (excluding bus errors) the affected outputs are switched off
immediately (without delay). In this case, only stop category 0 is supported.
WARNING
Selecting the wrong switch-off delay can result in incorrect safety distances being
designed.
When designing the safety distances, take the selected switch-off delay into
consideration.
For switch-off, please take into consideration the following:
Switch-off can be interrupted by switching the output on again.
If the parameterization of the module is modified, the modified
parameterization does not take effect until all the outputs have been
switched off.
If the parameterization is modified before switch-off is complete, a
diagnostic message is generated.
If the parameterization is modified, this can result in delayed startup due
to the switch-off delay.
Carry out a validation every time the parameterization is modified.
Bosch Rexroth AG
Parameterization of the module
Switching off outputs
Once the set switch-off delay has elapsed
Once the set switch-off delay has elapsed
Immediately (only stop category 0)
Delayed switch-off
Incorrect/insufficient safety distances
31/82