Pid - Delta C1000 Operation And Installation Manual

Photovoltaic inverter
Table of Contents

Advertisement

Parameter
Fac Low Off Slow
Fac Low On Slow
Fac Low Off Slow T
Reconnection Time
Once you change any item listed above, the country will be turn to "Custom".
You can go back the original country via re-selecting the country in the page
"Install settings" - "Country".

5.3.7.3.3 PID

The PID function default action time is set with 0, user can set the time from
0-10 or Auto. It will be started the function at 1 minutes after No DC, and will be
stop the function when DC voltage is input.
Install Settings – 2/2
PID
User Mode
The function is same as Fac Low Off, but the value must be higher than
former.
The function is same as Fac Low On, but the value must be higher than
former.
The function is same as Fac High Off T, but the time must be longer
than former.
The countdown time before inverter connected to grid.
Table 5-2 : Grid Setting Parameters (Continued)
21. Jun 2010 13:50
[
] Hour
0
Figure 5-16 : PID function settings
Description
NOTE
Install Settings – 2/2
Reconnection Time
Ramp
-up Power
PID
Installer Mode
57
Turn on PV Inverter
21. Jun 2010 13:50
[
60
]
S
[
]
%/
m
20
[
] Hour
0