Delta C1000 Operation And Installation Manual page 27

Photovoltaic inverter
Table of Contents

Advertisement

DC Terminal
DC Cable
(Cu)
DC Cable
(Al)
* Maximum cable size allowed for DC+/DC- → 240 mm
CAUTION! RISK OF SHORT CIRCUIT AND FIRE!
- The working temperature of power cable should be at least 105°C.
- To avoid damage of cables, please install the movable bushing to the DC & AC side
bottom plate before wiring. (Please refer to Appendix B for installing procedure)
!
- To prevent moisture, dust or living creature from entering the case, please seal the
DC & AC side bottom plate with high temperature resistance and water-proof
material (Ex: fire retardant cable sealant or silicon)
Need to use moving bushing and silicon rubber for waterproof and dust.
The recommended material of movable bushing and silicon rubber is shown as below:
Component
Movable bushing
Silicon rubber
For cables and terminals:
Delta recommends the cables used should be flexible unarmored multi-strand
and with suitable ampacity.
Delta would highly recommend that the material surface of copper wire /
aluminum wire lug should be tin or nickel electroplated.
Extreme temperature rise at the clamping point
If the contact resistance between the aluminum conductor and clamping point is too
high, the clamping point can become very hot and even catch fire in extreme cases.
To ensure a safe and reliable contact, always perform the following work steps:
Please select the Al wire size according to rules due to lower conductivity of Al.
Keep the installation location as free as possible from moisture or corrosive
atmospheres.
Connect the aluminum cables quickly.
Tighten the clamping screw in the clamping body with the maximum permissible
tightening torque.
No. of
conductor (+/-)
12 ~ 14
Minimum cable size requirement for DC+/DC-
70 mm
2
(14 Runs) / 95 mm
Minimum cable size requirement for DC+/DC-
95 mm
2
(14 Runs) / 120 mm
NOTE
Part number
1010-12
RTV162
NOTICE
Screw/Nut size
M10
2
(≧12 Runs)
2
(≧12 Runs)
2
Vendor
EMKA
GE Bayer Silicones
27
Installation
Torque requirement
(Nm)
25

Advertisement

Chapters

Table of Contents
loading

Table of Contents