DC Terminal
DC Cable
(Cu)
DC Cable
(Al)
* Maximum cable size allowed for DC+/DC- → 240 mm
Maximum No. of conductor
AC Terminal
AC Cable
(Cu)
The minimum requirement of individual cable size and numbers for each phase AC cable.
AC Cable
(Al)
The minimum requirement of individual cable size and numbers for each phase AC cable.
Maximum No. of conductor
PE Terminal
PE Cable
(Cu)
PE Cable
(Al)
No. of
conductor (+/-)
12 ~ 14
Minimum cable size requirement for DC+/DC-
70 mm
2
(14 Runs) / 95 mm
Minimum cable size requirement for DC+/DC-
95 mm
2
(14 Runs) / 120 mm
for each phase
8 (<300 mm
2
)
Minimum total cable size requirement for each phase
Minimum total cable size requirement for each phase
(DC/AC/Outside)
4/4/1
Minimum total cable size requirement
Minimum total cable size requirement
Appendix D-3 : Assembly Note - 3
DC
Screw/Nut size
M10
2
(≧12 Runs)
2
(≧12 Runs)
2
AC
Screw/Nut size
M12
1110 mm
2
150 mm
x 8
2
1480 mm
2
185 mm
2
x 8
PE
Screw/Nut size
M12
555 mm
2
740 mm
2
88
Appendix D: Assembly Note
Torque requirement
(Nm)
25
Torque requirement
(Nm)
45
Torque requirement
(Nm)
45