Type of Equipment
Model
Input
Absolute maximum
PV input voltage
Operation voltage range
Maximum power MPPT range
MPPT accuracy
Inverter wake up voltage
Startup voltage
MPP tracker
Input current limitation
Maximum input short circuit current
Input detection tolerance
DC breaker
Input protection
Output
Output capacity
Grid
Utility voltage range
Utility frequency
Utility frequency range
Maximum output current
Anti-islanding
Output reconnect
Reconnect time
Appendix A: Type of Equipment
C1000
1100Vdc
> 1000Vdc, INV Stop
520Vdc – 1000Vdc
550Vdc – 850Vdc
> 99.9% at rated power
> 200Vdc (Aux-power on)
570Vdc
2050A
2500A
Input voltage deviation < 2%
250A×14 Runs
DC over voltage_electronic shutdown
DC current limitation_current control
Surge arrestor_1100V/40kA Type 2
1000kW / 1000kVA
Three phase (3P3W-IT)
350VΔ ±10%
50/60Hz
Domestic regulation (Max 50/60Hz ± 5Hz)
1650A
Domestic regulation
Connect to utility after utility recover and
countdown finished
Domestic regulation