11.2.1 Temperature issues

Issue
Low heat
Temperature exceeds
mercury thermostat setting
One or more zones do not
heat properly
Temperature issues
Diagnosis
Operating temperature
too low.
Load configuration
improperly set up.
Boiler undersized.
Air trapped within
system.
Improper system
piping.
System pump
undersized.
Defective thermostat.
Boiler cycling on
operating/ safety
controls.
System radiation
undersized.
Incorrect anticipator
setting.
Thermostat not level.
Air trapped within zone
(s) piping
Low radiation/
excessive heat loss.
Low flow rate to zone
(s).
Defective zone valve/
zone circulator.
58
Section: Troubleshooting
Fix
Increase temperature target.
Review load configuration parameters.
Refer to Load Calculation vs. Boiler
Output.
Bleed system as required.
Refer to recommended piping guidelines
for the respective boiler model.
Check pump manufacturer's data.
Refer to manufacturer's instructions.
Check operation with
Ohmmeter/Voltmeter.
Check manufacturer's rating tables for
capacity per foot.
Check with Ammeter.
Check level.
Vent system/zone as required.
Check actual length of pipe using
radiation / heat loss calculation.
Check temperature drop across zone.
Check operation per manufacturer's
instructions.