Project Planning Using Device Description; Profinet Address And Identifying A Device - Pepperl+Fuchs PXV F200-B17-V1D Series Manual

Data matrix positioning system
Hide thumbs Also See for PXV F200-B17-V1D Series:
Table of Contents

Advertisement

PXV...-F200-B17-V1D
Operation and communication
5.1.3

Project Planning Using Device Description

As with PROFIBUS DP, a field device is integrated into the project planning tool by way of a
device description. The field device properties are described in the GSD file. The GSD file con-
tains the field device data that you need to operate the device in a PROFINET network. This
includes technical features and information about communication.
Import the GSD file into a project planning tool. Assign peripheral addresses to the individual
channels of the field devices as usual. The peripheral input addresses incorporate the received
data. The user program evaluates and processes this data. The user program generates the
peripheral output values and sends them to the control interface.
Once project planning is complete, the IO controller receives the project planning and configu-
ration data. The IO controller parameterizes and configures the field devices automatically.
Downloading the GSD File
You can find the relevant GSD file in the Software section of the product detail page for the
device.
To access the product detail page for the device, go to http://www.pepperl-fuchs.com and type
e.g., the product description or the item number into the search function.
5.1.4

PROFINET Address and Identifying a Device

Every PROFINET IO device has a unique device identification. This device identification is
comprised from the following:
A unique MAC ID. This MAC ID is printed on the back of the device.
A device name. The default device name for the product as delivered is pcv-f200.
An IP address. The default IP address for the product as delivered is 192.168.2.2.