5.2.2 Sub-FC04 (0x04): Set the Modbus Unit ID (Net ID)
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
New
Address
04
[reserved]
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Result
04
[reserved]
Note: This parameter setting is effective after power cycling the module,
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-7: FC100-Sub-FC04 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x04
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x00
Table 5-8: FC100-Sub-FC04 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x04
1 Byte
0x00 => OK,
Others => Error
1 Byte
0x00
Version 1.1