Sub-Fc70(0X46): Get 8 Locked Periods; Get 8 Locked Periods - ICP DAS USA ACS-20B-MRTU User Manual

No-touch infrared sensor switch
Table of Contents

Advertisement

5.2.27 Sub-FC70(0x46): Get 8 Locked Periods

This command gets 8 locked periods in a day from module. One locked period composed
of Start Time and End Time. The End Time should be late after the Start Time.
Byte
Description
order
00
Address
01
FC
02
Sub-FC
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
P1 Start Hour
04
P1 Start Minute
05
P1 Start Second
06
P1 End Hour
07
P1 End Minute
08
P1 End Second
09~44 P2 to P7 ...
45
P8 Start Hour
46
P8 Start Minute
47
P8 Start Second
48
P8 End Hour
49
P8 End Minute
50
P8 End Second
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-57: FC100-Sub-FC70 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x46
Table 5-58: FC100-Sub-FC70 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x46
1 Byte
0 ~ 23, period 1 start Hour
1 Byte
0 ~ 59, period 1 start Minute
1 Byte
0 ~ 59, period 1 start second
1 Byte
0 ~ 23, period 1 end Hour
1 Byte
0 ~ 59, period 1 end Minute
1 Byte
0 ~ 59, period 1 end second
36 Bytes
period 2 ~ 7 start time and end time
1 Byte
0x00
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
1 Byte
0x00
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
1 Byte
0x00
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
Version 1.1
E-mail: service@icpdas.com
53
Page:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs-20w-mrtu

Table of Contents