5.2.15 Sub-FC42(0x2A): Get IR Sensing Record Mode
Byte
Description
order
00
Address
01
FC
02
Sub-FC
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Record
mode
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-33: FC100-Sub-FC42 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x2A
Table 5-34: FC100-Sub-FC42 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x2A
1 Byte
The way of storing records when storage full:
0=> (default) Clear all records and store from
start.
1=> Discard new data and keep 1600 records
of old data.
Version 1.1
E-mail: service@icpdas.com
41
Page: