7.2.4 04(0x04) Read the Input Registers (Read AI values)

This function code is used to read either the input registers or the current analog input value from
the iNS-308. These registers are also used to store the current value for the digital counter, the
number of DI channels and the number of DO channels, etc.
[Request]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02-03
Starting AI Address
Number of Registers
04-05
(Channels)
[Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02
Byte Count
03
Register Values
[Error Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02
Exception Code
Copyright © 2022 ICP DAS CO., Ltd. All Rights Reserved.
Size
1 Byte
1 to 247
1 Byte
0x04
Byte 02 = high byte
2 Byte
Byte 03 = Low byte
Word Count
2 Byte
Byte 04 = high byte
Byte 05 = Low byte
Size
1 Byte
1 to 247
1 Byte
0x04
Byte Count of the Response
1 Byte
( n = Points x 2 Byte )
n= 1; Byte 03 = high byte
n= 2; Byte 04 = Low byte
n Byte
.......
n= m; Byte m+1 = high byte
Byte m+2 = Low byte
Size
1 Byte
1 to 247
1 Byte
0x84
Refer to the Modbus Standard
1 Byte
Specifications for more details
Value
Value
Value
- 39 -