5.2.3 Sub-FC05 (0x05): Get Communication Settings

Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
reserved
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Net ID
04
Baud rate
05
Parity
06
Data bits
07
Stop bits
08
Modbus
response
delay
09
Reserved
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-9: FC100-Sub-FC05 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x05
1 Byte
0x00
Table 5-10: FC100-Sub-FC05 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x05
1 Byte
1 ~ 247 (Net ID) of the module
1 Byte
6 ~ 10 (baud rate index)
=> {9600, 19200, 38400, 57600, 115200} bps
1 Byte
0, 1, 2=>{None, Odd, Even} (default: None)
1 Byte
8 (fixed)
1 Byte
1, 2 (default: 1)
1 Byte
0 ~ 30 ms (default: 1 ms)
1 Byte
0x00
Version 1.1
E-mail: service@icpdas.com
29
Page: