5.2.4 Sub-FC06 (0x06): Set Communication Settings
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
New NetID
04
Baud rate
05
Parity
06
Reserved
07
Stop bits
08
Modbus
response
delay
09
Change
Setting
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Result
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-11: FC100-Sub-FC06 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x05
1 Byte
1 ~ 247 (Net ID) of the module
1 Byte
6 ~ 10 (baud rate index)
=> {9600, 19200, 38400, 57600, 115200} bps
1 Byte
0, 1, 2=>{None, Odd, Even} (default: None)
1 Byte
0x00
1 Byte
1, 2 (default: 1)
1 Byte
0 ~ 30 ms (default: 1 ms)
1 Byte
0=>The settings are effective after power
cycling.
1=>Change settings immediately
Table 5-12: FC100-Sub-FC06 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x05
1 Byte
0=>OK
0xFF=>Error
Version 1.1
E-mail: service@icpdas.com
30
Page: