Sub-Fc69(0X45): Set Enabled State Of Locked Periods; Set Enabled State Of Locked Periods - ICP DAS USA ACS-20B-MRTU User Manual

No-touch infrared sensor switch
Table of Contents

Advertisement

5.2.26 Sub-FC69(0x45): Set Enabled State of Locked Periods

This command gets the enable/disable status of the 8 locked periods in a day by one
byte with 8 bits
disabled. E.g. 0x73 (hex) = 0111 0011 (binary) means 5 locked periods are enabled.
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Reserved
04
Every day
enabled state
05
Reserved
06
Sunday
enabled state
07
Reserved
08
Monday
enabled state
09
Reserved
10
Tuesday
enabled state
11
Reserved
12
Wednesday
enabled state
13
Reserved
14
Thursday
enabled state
15
Reserved
16
Friday enabled
state
17
Reserved
18
Saturday
enabled state
Byte order
Description
00
Address
01
FC
02
Sub-FC
03
Result
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
(b7~b0=>P8~P1)
Table 5-55: FC100-Sub-FC69 Request
Size
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
Table 5-56: FC100-Sub-FC69 Response
Size
1 Byte
1 Byte
1 Byte
1 Byte
where bit value = 1 means enabled and bit value = 0
Value
1 ~ 247 (Net ID)
0x64
0x45
0x00
0x00 => Every day mode (default)
0x01 => Weekday mode
0x00
0x00 ~ 0xFF, enabled state of 8 periods
0x00
0x00 ~ 0xFF, enabled state of 8 periods
0x00
0x00 ~ 0xFF, enabled state of 8 periods
0x00
0x00 ~ 0xFF, enabled state of 8 periods
0x00
0x00 ~ 0xFF, enabled state of 8 periods
0x00
0x00 ~ 0xFF, enabled state of 8 periods
0x00
0x00 ~ 0xFF, enabled state of 8 periods
Value
1 ~ 247 (Net ID)
0x64
0x45
0x00 => OK
0xFF => Error
Version 1.1
E-mail: service@icpdas.com
52
Page:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs-20w-mrtu

Table of Contents