5.2.28 Sub-FC71(0x47): Set 8 Locked Periods

This command sets 8 locked periods in a day to module. One locked period composed of
Start Time and End Time. The End Time should be late after the Start Time.
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
P1 Start Hour
04
P1 Start Minute
05
P1 Start Second
06
P1 End Hour
07
P1 End Minute
08
P1 End Second
09~44 P2 to P7 ...
45
P8 Start Hour
46
P8 Start Minute
47
P8 Start Second
48
P8 End Hour
49
P8 End Minute
50
P8 End Second
Byte order
Description
00
Address
01
FC
02
Sub-FC
03
Result
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-59: FC100-Sub-FC71 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x47
1 Byte
0 ~ 23, period 1 start Hour
1 Byte
0 ~ 59, period 1 start Minute
1 Byte
0 ~ 59, period 1 start second
1 Byte
0 ~ 23, period 1 end Hour
1 Byte
0 ~ 59, period 1 end Minute
1 Byte
0 ~ 59, period 1 end second
36 Bytes
period 2 ~ 7 start time and end time
1 Byte
0x00
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
1 Byte
0x00
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
1 Byte
0x00
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
Table 5-60: FC100-Sub-FC71 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x47
1 Byte
0x00 => OK
Others => Error, bit0~bit7 correspond to
period1~period8. Bit value=1 means invalid
settings.
Version 1.1