5.2.20 Sub-FC47(0x2F): Set Relay Hold Time

Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Relay hold
time MSB
04
Relay hold
time LSB
Byte
Description
order
00
Address
01
FC
02
Sub-FC
03
Result
ACS-20B(W)-MRTU User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
Table 5-43: FC100-Sub-FC47 Request
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte

0x2F

1 Byte
High byte of relay hold time (500~20,000ms)
e.g. 0x03 of 0x03E8 (1,000 ms)
1 Byte
Low byte of relay hold time (500~20000ms)
e.g. 0xE8 of 0x03E8 (1,000 ms)
Table 5-44: FC100-Sub-FC47 Response
Size
Value
1 Byte
1 ~ 247 (Net ID)
1 Byte
0x64
1 Byte
0x2F
1 Byte
0x00 => OK
0xFF => Error
Version 1.1