It should be pointed out that even by simply touching the bulb with the fingers, it is possible to leave a slight
greasiness which could compromise the working of the UV photoelectric cell.
The UV cell does not "see" daylight or light from an ordinary lamp. It is possible to verify its sensibility with a
flame (or cigarette lighter or a candle) or with the electric spark that occurs between electrodes in an ordinary
ignition transformer. To ensure that the UV cell works properly, its current value should be sufficiently stable
so as not to fall below the minimum value required for the specific control box. It may be necessary to search
experimentally for the best position by sliding (axial or rotation movement) the body that contains the photoe-
lectric cell in respect to the fastening clamp. An inspection can be carried out by inserting a microammeter,
with an adequate scale, in series to one of the two UV photoelectric cell connection wires.
It is obviously necessary to respect the polarity + and -). For the LFL.... control box, the value of the cell current
should be from 70 microamperes to 630 microamperes (the value is shown on the wiring diagram).
11) With the burner operating at a minimum (ignition flame valve and safety valve open and servomotor which
regulates delivery (gas/air) at a minimum), immediately check visually the entity and appearance of the fla-
me and, if necessary, proceed with correcting it by operating the gas delivery regulator of the ignition flame
(pilot) and/or the adjustable screws of the disk which regulates the gas and air delivery. Subsequently, check
the quantity of gas delivered by reading the meter. See Chapter "Reading the meter". If necessary, correct
the gas and relative combustion air delivery by operating as described in point 7. The control combustion
with the appropriate instruments. For a correct air/gas ratio, the percentage of Carbon Dioxide (CO
increase together with the increase in delivery. As an indication, for methane gas, the percentage should be
from at least 8 % at minimum burner delivery to an optimum value of 10 % for maximum delivery.
We advise against exceeding the value of 10 % to avoid operating with a rather limited excess of air which
could cause (variation in atmospheric pressure, presence of dust particles in fan's air ducts) a considerable
amount of Carbon Monoxide (CO). It is indispensable to check, with the appropriate instrument, that the Carbon
Monoxide (CO) present in the smoke does not exceed the maximum level permitted of 0, %.
12) After having regulated at "minimum", put the modulation switches in the "MAN" (manual) and "MAX" (maxi-
mum) positions.
13) The servomotor regulating gas/air delivery starts up, the "V" cam contact closes (see BT 8562/1) and voltage
arrives at the principle gas valve which then opens. Wait until the disk on which the regulating screws have
been fitted, has reached an angle of about 12° (this corresponds to the space taken up by three screws),
and then stop modulation and return the switch to the "O" position. Carry out a visual control of the flame and
proceed, if necessary, with regulating the combustion air and the gas by operating the adjustable screws of
the regulating disk. The operation described above should be repeated progressively (by moving forward the
disk about 12° at a time) and modifying every time, if necessary, the fuel/air ratio during the whole modulation
run. Make sure that the increase in fuel delivery occurs gradually and that maximum delivery is reached at
the end of the modulation run. This is necessary in order to ensure that the modulation functions with good
graduality. The positions of the screws that commend the fuel may need to be modified in order to obtain the
graduality required.
14) With the burner operating at maximum delivery required for the boiler, check combustion with the appro-
priate instruments and modify, if necessary, the previous regulation carried out after a visual control only
(CO
max. = 0 % - CO max. = 0, %).
2
15) We recommend controlling the combustion with the appropriate instruments and, if necessary, modify the pre-
vious regulation carried out, after a visual control only, also in a few intermediate points of the modulation run.
16) Check that modulation functions automatically by putting the AUT - O - MAN switch in the "AUT" position and
the MIN - O - MAX switch in the "O" position. In this way, modulation is activated exclusively by the automatic
command of the boiler's probe, if the burner is a modulating version, or on the command of the thermostat or
pressure switch of the 2nd stage, if the burner is a two-stage progressive version. (See Chapter "Electronic
Potentiality Regulator RWF 40 for the modulating version).
7) The air pressure switch
has the job of bringing the control box to a safety shut down if the air pressure is not at the correct value.
Therefore, the air pressure switch must be regulated in such a way as to intervene by closing the contact
(foreseen to be closed while working) when the air pressure in the burner has reached a sufficient level.
The pressure switch is self-controlled and therefore it must close the contact (fan stops and consequently
there is an absence of air pressure in the burner; if it does not, the control box will not be inserted (the burner
remains at a standstill). It must be specified that if the contact is not closed during working (insufficient air
pressure), the control box will carry out its cycle, but the ignition transformer will not be inserted and the gas
pilot valves will not open. Consequently, the burner will go to "shut down". Check that the air pressure switch