Application parameters
Application parameters are parameter-specific for the selected application.
Display image
P_1901
P_1902
System, 1=He, 2=Co, 3=ChOv, 4=HC, 5=R
Min 1
0=ext.temp, 1 or 2 room units
Min 0
P_1903
Frost guard temp
Min 5
P_1904
Economy mode available?
Min 0
P_1907
Night cool, Set point
Min 10
P_1908
Actuator Cool, 1=NC, 2=0-10V, 3=NO, 4=CCO
Min 1
P_1909
Window, 0=NP, 1=NC, 2=NO, 3=CODry
Min 0
P_1910
Occupancy, 0=NP, 1=NC, 2=NO
Min 0
P_1911
RU back to auto state
Min 0
P_1912
Room unit´s min set point
Min 0
20210201
Description
Indicates how the climate
4
system should operate for
heating and cooling.
1 = Heating only, 2 = Cooling
Max 5
only, 3 = Change-over function
4 = Heating/Cooling, 5 =
Heating with radiator
Indicates whether one or
1
two room units are used. If 2
units are used they should be
connected with a cable.
Max 2
0 = ext.temp, 1 = 1 unit
2 = 2 units
Indicates at which temperature
10 °C
the frost protection should
switch in.
Max 12
Indicates whether the Economy
1
mode is available.
0 = No
1 = Yes
Max 1
Indicates the temperature
18 °C
setpoint applicable to the Night
cool function.
Max 32
Cooling actuator type.
1
1=Normally closed
2= 0-10V
3=Normally open
Max 4
4=CCO
Window contact type.
0
0=Not used
1=Normally closed
2=Normally open
Max 3
3=Dry switch for changing cool/
heat in change-over system
Indicates whether a presence
0
detector is installed and if so
how it is installed.
0 = No contact installed
Max 2
1 = Normally closed
2 = Normally open
Indicates how long after the
480 min
most recent manual room
temperature adjustment that
the controller should return to
Max 1200
the AUTO mode.
0 = Not used
Indicates which lowest
16 °C
temperature is possible to
adjust manually on the room
unit in the MAN operating
Max 50
mode.