Display image
P_1949
P term SA1 Scale 1:100
Min 1
P_1950
I term SA1 Scale 1:100
Min 1
P_1951
P term SA2 Scale 1:100
Min 1
P_1952
I term SA2 Scale 1:100
Min 1
P_1953
P term EA Scale 1:100
Min 1
P_1954
I term EA Scale 1:100
Min 1
P_1955
SA1 calc. type, 1=Ana, 2=MB
Min 1
P_1956
SA1 K-term, Scale 1:10
Min 1
P_1957
SA2 calc. type, 2=MB
Min 2
P_1958
SA2 K-term, Scale 1:10
Min 1
P_1959
EA calc. type, 2=MB
Min 2
P_1960
EA K-term, Scale 1:10
Min 1
150
Max 10000
50
Max 10000
150
Max 10000
50
Max 10000
150
Max 10000
50
Max 10000
2
Max 2
50
Max 15000
2
Max 2
50
Max 15000
2
Max 2
50
Max 15000
20210201
Swegon reserves the right to make design changes.
CONDUCTOR W4
Description
Indicates the value for P in
supply air duct 1. A high value
denotes faster control. A low
value denotes slower control.
Indicates the value for I in
supply air duct 1. A high value
denotes faster control. A low
value denotes slower control.
Indicates the value for P in
supply air duct 2. A high value
denotes faster control. A low
value denotes slower control.
Indicates the value for I in
supply air duct 2. A high value
denotes faster control. A low
value denotes slower control.
Indicates the value for P in the
extract air duct. A high value
denotes faster control. A low
value denotes slower control.
Indicates the value for I in the
extract air duct. A high value
denotes faster control. A low
value denotes slower control.
Indicates how the controller
calculates the airflow in supply
air duct 1 in relation to the
C-factor.
1=Linear Analogue pressure sensors
2=Quadratic of MB pressure sensor.
Indicates the C-factor for
actuator downstream of supply
air duct 1.
Resolution = 1:10
Indicates how the controller
calculates the airflow in supply
air duct 2 in relation to the
C-factor.
2=Quadratic of MB pressure
sensor.
Indicates the C-factor for supply
air duct 2.
Indicates how the controller
calculates the airflow in the
extract air duct in relation to
the C-factor.
2 = Quadratic of the MB
pressure sensor.
Indicates the C-factor for the
extract air duct.
61