Application Parameters W1 - Swegon CONDUCTOR W1 Technical Manual

Table of Contents

Advertisement

Application parameters W1

Application parameters are parameter-specific for the selected application.
Display image
P_1101
System1=H,2=C,3=ChOv,4=HC
min
1
P_1102
0=ext.temp, 1 or 2 room units
min
0
P_1103
Frost guard temp.
min
5
P_1108
Economy mode available
min
0
P_1109
ActuatorCool 1=NC, 2=0-10V, 3=NO
min
1
P_1110
ActuatorHeat 1=NC, 2=0-10V, 3=NO
min
1
P_1111
Window 0=NP
min
0
P_1112
Occupancy 0=NP
min
0
P_1113
P term Change over
min
1
P_1114
I term Change over
min
1
Description
Indicates how the climate
4
system should operate for
heating and cooling.
1 = Heating only
2 = Cooling only
max 4
3 = Change-over function
4 = Heating/Cooling
Indicates whether one or
1
two room units are used. If 2
units are used they should be
connected with a cable.
0 = The controllers temp.
max 2
sensor is used, 1 = 1 unit
2 = 2 units
Indicates at which temperature
10
C
the frost protection should
switch in.
max 12
Indicates whether the Economy
1
mode is available.
0 = No
1 = Yes
max 1
Indicates which sort of valve
1
actuator is installed in the
cooling water circuit
(1=24V-NC, 2=0-10V, 3=24V-
NO)
max 3
Indicates which sort of valve
1
actuator is installed in the
heating water circuit..
(1=24V-NC, 2=0-10V, 3=24V-
NC)
max 3
Indicates whether a window
0
contact is installed and if so
how it is installed.
0 = No contact installed
max 0
Indicates whether a presence
0
detector is installed and if so
how it is installed.
0 = No contact installed
max 0
Indicates the value for P for the
5000
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
max 10000
Indicates the value for I for the
50
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
max 10000