Swegon CONDUCTOR W4 Technical Manual page 68

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

CONDUCTOR W4
Conductor W4 BMS, applies to software from 1.48
Default values from parameter file
Input Status
Discrete Input (1 bit)
Modbus
Name
1x0028
Short circuit X13
1x0029
Short circuit X14
1x0030
SPI Flash broken
1x0031
Radio chip broken
1x0032
Parameter file revision
1x0033
Parameter file format
1x0034
No ModBus ID
1x0035
No Application
1x0036
No parameters
1x0037
Parameter missing
1x0038
Parameter value error
1x0039
Parameter file size
1x0040
Wrong parameter file
1x0041
Check Duct Group SM
1x0042
Check Duct Group DC
1x0043
Previous parameters are lost
1x0044
Factory parameters take up
1x0045
Not used
1x0046
Not used
1x0047
No supply pressure from AHU
1x0048
No exhaust pressure from AHU
1x0049
Supply duct 100% open
1x0050
Exhaust duct 100% open
1x0051
Low voltage detect
1x0052
Not used
1x0053
Duct group member missing
1x0054
Negative pressure
68
Swegon reserves the right to make design changes..
Read only
Min/Max
Remarks
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, resets after right parameters
0/1
ALARM, resets after right parameters
0/1
ALARM, requires HW reset
0/1
ALARM, requires HW reset
0/1
ALARM, resets automatically
0/1
ALARM, resets automatically
0/1
ALARM, resets automatically
0/1
ALARM, resets automatically
0/1
ALARM, resets automatically
0/1
ALARM, resets automatically
0/1
ALARM, resets automatically
20210201
Default