Swegon CONDUCTOR W4 Technical Manual page 47

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

RF Quality
RF-pair up
RF Quality
Language
<Exit
Select>
Figure 12. Imaage for selecting the RF Quality and the RF connection image.
If no cable is connected between the controller and the room unit, the two
will communicate with one another via radio signals.
1.
Go to the Service menu.
2.
Highlight Settings.
Press OK or on the ►Right key.
3.
4.
Highlight RF pair up
Press OK or on the ►Right key.
5.
Start the test by the ► Right key.
6.
During the test, 100 messages are sent between the controller and
the room unit. The room unit calculates the number of successful
transmissions and displays them in the image.
The test can be cancelled by pressing the ► Right key.
Press the ◄ Left key when the test is finished to return to the Settings
7.
menu.
Return to the Service menu by pressing the ◄Left key.
8.
RF connection
RF pair up: 100
<Exit
20210201
Swegon reserves the right to make design changes.
CONDUCTOR W4
Start
47