CONDUCTOR W4
Display image
58
Swegon reserves the right to make design changes..
P_1913
Room unit´s max set point
Min 0
P_1914
Heat ON limit
Min 5
P_1915
Heat OFF limit
Min 5
P_1916
Delay between heat ON/OFF
Min 1
P_1917
P term Heating Scale 1:100
Min 1
P_1918
I term Heating Scale 1:100
Min 1
P_1919
P term Cooling Scale 1:100
Min 1
P_1920
I term Cooling Scale 1:100
Min 1
P_1921
P term Change over
Min 1
P_1922
I term Change over
Min 1
P_1923
C02 Control, 0=No, 1=Active
Min 0
P_1924
C02 min level ppm
Min 350
Description
Indicates which highest
28 °C
temperature is possible to
adjust manually on the room
unit in the MAN operating
Max 50
mode.
Indicates at which output signal
10 %
for heating the relay contact
closes and the heat source is
opened.
Max 50
Indicates at which output signal
5 %
for heating the relay contact
opens and the heat source is
disconnected.
Max 10
Indicates what the delay
5 min
should be between when the
heat source is connected or
disconnected. The purpose
Max 25
of this is to prevent the relay
contact from closing and
opening too often.
Indicates the value for P for
5000
heating. A high value denotes
faster control. A low value
denotes slower control.
Max 10000
Indicates the value for I for
5
heating. A high value denotes
faster control. A low value
denotes slower control.
Max 10000
Indicates the value for P for
5000
cooling. A high value denotes
faster control. A low value
denotes slower control.
Max 10000
Indicates the value for I for
5
cooling. A high value denotes
faster control. A low value
denotes slower control.
Max 10000
Indicates the value for P for the
5000
Change Over function. A high
value denotes faster control.
A low value denotes slower
Max 10000
control.
Indicates the value for I for the
5
Change Over function. A high
value denotes faster control.
A low value denotes slower
Max 10000
control.
Indicates whether the installed
0
carbon dioxide sensor is
connected or not.
0 = Not connected
Max 1
1 = Connected
Indicates at which lowest
500 ppm
carbon dioxide content in
the room the airflow should
increase.
Max 1000
20210201