Swegon CONDUCTOR W4 Technical Manual page 56

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

CONDUCTOR W4
Display image
P_108
min
P_109
min
P_110
min
P_111
min
P_112
min
P_113
min
P_114
min
P_118
min
P_119
min
P_120
min
P_121
min
P_122
min
P_123
min
56
Swegon reserves the right to make design changes..
Valve exercise (h) 0=Not used
0
max 168
Motion timer delay (min)
0
Warning delay from start-up (min)
0
Warning delay, PI-overload (min)
0
Warning delay, Set point (min)
0
Warning delay, pressure sensor (min)
0
Room Number (optional)
0
Zero calibration (h) 0=not used
0
Zero calibration wait (min)
1
BMS Modbus Address
1
Condense sensor measure method
0
Condense sensor wet limit
0
max 10000
Condense sensor dry limit
100
max 10000
Description
Indicates how often the valves should
96
hour
be exercised (how many hours shall pass
between two exercise runs).
Indicates the number of minutes after which
20
min
the controller should switch from AUTO to
ECON after the last occupant has left the
room.
max 60
Indicates after how many minutes after
60
min
start-up the controller is allowed to initiate
an alarm.
The alarm is deactivated when the time delay
= 0.
max 720
Indicates after how many minutes the system
120 min
should initiate an alarm for a +100% or
-100% output signal.
The alarm is deactivated when the time delay
= 0.
max 720
Indicates after how many minutes the system
120 min
should initiate an alarm, if the set point for
temperature, flow or pressure has not been
reached.
The alarm is deactivated when the time delay
max 720
= 0.
Indicates after how many minutes the system
30
min
should initiate an alarm if no pressure or flow
sensor is detected.
The alarm is deactivated when the time delay
= 0.
max 720
Indicates the room number.
0
max 32000
O-point calibration of
0
h
MB pressure sensor. Enter hours between
calibration.
max 720
Delay before calibration starts. (to allow the
3
min
dampers time to close)
max 6
Modbus address for the pipe work contractor
set
2
ID
in BMS mode (Modbus 1)
max 247
Choice of method for condensation
1
measurement 0=Fixed limits, 1=Adjustable
limits
max 1
Condensation sensor wet limit. Active when
500 kOhm
P_121=1
Condensation sensor dry limit. Active when
900 kOhm
P_121=1
20210201