Swegon CONDUCTOR W4 Technical Manual page 70

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

CONDUCTOR W4
Conductor W4 BMS, applies to software from 1.48
Default values from parameter file
Holding
16 bit integer register
register
Modbus
Name
4x0037
Not used
4x0038
Economy flow, % of
normal flow
4x0039
NHoliday flow, % of
normal flow
4x0040
Not used
4x0041
Not used
4x0042
Boost flow SA1
4x0043
Boost flow SA2
4x0044
Not used
4x0045
Not used
4x0046
Not used
4x0047
Not used
4x0048
P term Heat
4x0049
I term Heat
4x0050
P term Cool
4x0051
I term Cool
4x0052
P term Change over
4x0053
I term Change over
4x0054
SA 0% value
4x0055
SA 100% value
4x0056
EA 0% value
4x0057
EA 100% value
4x0058
Not used
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
4x0064
Relative flow in manual
mode
4x0065
Not used
4x0066
CO2 min level
4x0067
CO2 max level
4x0068
CO2/Volt
4x0069
Copy of Coil Status 1-16
70
Swegon reserves the right to make design changes..
R/W
Min/Max
Remarks
0/100
(%)
0/100
(%)
0/5000
l/s
0/5000
l/s
1/10000
Scale 1:100
1/10000
Scale 1:100
1/10000
Scale 1:100
1/10000
Scale 1:100
1/10000
Scale 1:100
1/10000
Scale 1:100
0/5000
5000/10000
0/5000
5000/10000
0-50
(degC) Only used in Manual state
1/3
1=Eco flow, 2=Normal flow, 3=Boost
flow. Only used in Manual state
350/1000
(ppm)
350/2000
(ppm)
10/500
(ppm/volt)
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
...
Bit15=0x0016"
20210201
Default
0
10
30
30
5000
5
5000
5
5000
5
0
10000
0
10000
500
1000
200

Advertisement

Table of Contents
loading

This manual is also suitable for:

20210201

Table of Contents