Swegon CONDUCTOR W4 Technical Manual page 63

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

Display image
P_1972
Not used flow from Normal flow
Min 0
P_1973
Two step heating 1=OFF, 2=ON
Min 0
P_1974
Two step delay (min)
Min 0
P_1975
Relay use 0=OFF, 1=ON
Min 0
P_1976
Commissioning Air
Min 0
P_1977
Commissioning Water
Min 0
P_1978
Cold draught protection, 0=OFF
Min 0
P_1979
Cdp cool output level
Min 0
P_1980
4-pipe POS max
Min 0
P_1981
4pipe POS min
Min 0
P_1982
4pipe NEG max
Min 0
P_1983
4pipe NEG min
Min 0
10
Max 100
1
Max 1
5 min
Max 30
1
Max 1
0
Max 4
0
Max 2
0%
Max 100
30%
Max 100
100%
Max 100
65%
Max 100
55%
Max 100
20%
Max 100
20210201
Swegon reserves the right to make design changes.
CONDUCTOR W4
Description
Indicates what percentage
of the normal airflow will be
discharged into the room when
it is not occupied for a longer
period.
Activates provision for extra
heating output.
Indicates the time delay for
switching on extra heating.
Activates/deactivates the
controller's relay function.
Choice of commissioning
mode, Air
0=Off, 1=Airflow, No
occupancy, 2=Airflow, Min.
occupancy, 3=Airflow, Max.
occupancy, 4=Airflow, Holiday
Choice of commissioning
mode, Water
0=Off, 1=Cooling valve fully
open, 2=Heating valve fully
open
Indicates the level of the output
signal for heated water valve
actuators.
Indicates maximum cooling
load before the heat is switched
off.
Output signal's voltage level at
a heating signal of 100%
Output signal's voltage level at
lowest heating signal
Output signal's voltage level at
a cooling signal of 100%
Output signal's voltage level at
lowest cooling signal
63