Swegon CONDUCTOR W4 Technical Manual page 62

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

CONDUCTOR W4
Display image
62
Swegon reserves the right to make design changes..
P_1961
Actuator Heat 1=NO, 2=NC (On Relay, X-15)
Min 1
P_1962
Boost at arrival 0=No 1=Active
Min 0
P_1963
Boost at arrival time (min)
Min 1
P_1964
Conference, Office or VAV
Min 1
P_1965
ActuatorHeat 1=NC, 2=0-10V, 3=NO
(30-31-32, X-12)
Min 1
P_1966
TC_Normal
Min 15
P_1967
TH_Normal
Min 15
P_1968
TC_Economy
Min 10
P_1969
TH_Economy
Min 10
P_1970
TC_Holiday
Min 10
P_1971
TH_Holiday
Min 10
Description
Indicates the type of valve
2
actuators that are used to heat
water
1=24V-NC
Max 2
2=24V-NO
Indicates whether time-adjusted
1
flow boost is accessible.
(0=No, 1=Yes)
Max 1
Indicates how long the
5
timeadjusted flow boost should
be on ON when occupancy is
activated
Max 300
Select function. Conference
2
room (two supply air dampers)
hotel/office or VAV
1=W4.2 (Conference room)
Max 2
2=W4.1 (Hotel) 3=VAV
W4.1 function for actuator,
1
heat
1= Normally closed
2= 0-10V
Max 3
3= Normally open
Switch in cooling for normal
23
operation.
Max 35
Switch in heating for normal
21
operation.
Max 35
Switch in cooling for economic
25
operation.
Max 35
Switch in heating for economic
19
operation.
Max 35
Switch in cooling for holiday
27
operation.
Max 30
Switch in heating for holiday
17
operation.
Max 35
20210201

Advertisement

Table of Contents
loading

This manual is also suitable for:

20210201

Table of Contents