Swegon CONDUCTOR W4 Technical Manual page 32

Hide thumbs Also See for CONDUCTOR W4:
Table of Contents

Advertisement

CONDUCTOR W4
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Connect the damper motor for extract air as follows:
11. Connect the damper motor for supply air as follows:
32
Swegon reserves the right to make design changes..
Connect the valve actuator for cooling water to wiring terminals 27 and
29 respectively.
Connect the presence sensor to wiring terminals 12 and 26 respectively.
Connect the window contact (normally closed or normally open) to
wiring terminals 10 and 25 respectively.
Connect the pressure sensor to the Modular contact. Set the address
on sensor.
SA1 = 3
SA2 = 6
EA = 4
Connect the carbon dioxide sensor as follows:
0-10 V signal: Wiring terminal no. 16
G: Wiring terminal no. 21.
G0: Wiring terminal no. 22.
Connect the wires of the condensation sensor to wiring terminals
17 and 18 respectively. NOTE! May vary depending on the type of
condensation sensor.
Connect the wires of the temperature sensor to wiring terminals 19 and
20 respectively
Connect the secondary side cables of the transformer to wiring
terminals 23 (G) and 24 (GO) respectively.
Connect the valve actuator for heating water as follows:
Relay contact located under the casing of the controller.
To wiring terminal no. 30.
To wiring terminal no. 32.
G0: Wiring terminal no. 36.
0-10 V signal: Wiring terminal no. 37.
24 V: Wiring terminal no. 38.
G0: Wiring terminal no. 33.
0-10 V signal: Wiring terminal no. 34.
24 V: Wiring terminal no. 35.
20210201

Advertisement

Table of Contents
loading

This manual is also suitable for:

20210201