CONDUCTOR W4
Conductor W4 BMS, applies to software from 1.48
Default values from parameter file
Input
16 bit integer register
register
Modbus
Name
3x0051
PID SA Out
3x0052
PID EA Out
3x0053
Cool Water
3x0054
Warm Water
3x0055
SA Damper pos.
3x0056
EA Damper pos
3x0057
Airflow SA2
3x0058
Airflow SA1
3x0059
Airflow EA
3x0060
Room temp to controller
3x0061
Change over temp
3x0062
CO2 in room
3x0063
Copy of Input Status 1-16
3x0064
Copy of Input Status 17-32
3x0065
Copy of Input Status 33-48
3x0066
Copy of Input Status 49-64
72
Swegon reserves the right to make design changes..
Read only
Min/Max
Remarks
-100/100
(%)
-100/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
(l/s)
(l/s)
(l/s)
(degC) (if 2 RU, the average temperature
of these)
(degC)
ppm
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
...
Bit15=0x0016"
0/65535
"Bit0=0x0017
Bit1=0x0018
...
Bit15=0x0032"
0/65535
"Bit0=0x0033
Bit1=0x0034
..
Bit15=0x0048"
0/65535
"Bit0=0x0049
Bit1=0x0050
..
Bit15=0x0064"
20210201