Coding 2
(continued)
Overview of all codings (continued)
Coding as per
Function
factory setting
Address: Value
62: 10
DHW
67: 40
DHW
63: 0
DHW
63: 0
63: 0
DHW
DHW
68: 8
DHW
69: 7
DHW
76: 0
General
77: 1
General
78: 1
General
79: 0
General
80: 1
80: 1
General
General
Circulation pump with run-on time of
10 minutes
10 minutes
With Vitosolic:
3rd DHW set-point 40˚C/ 104˚F
3rd DHW set-point 40˚C/ 104˚F
Reloading suppression will be active
above set temperature. DHW tank is
heated only by solar heating system.
Without additional function for
domestic hot water heating
Without additional function for
Without additional function for
domestic hot water heating
domestic hot water heating
In conjunction with 2 tank
temperature sensors with the DHW
heating:
Switch-off point of tank heating at
setpoint value x 0.8
In conjunction with 2 tank
temperature sensors with the DHW
heating:
Switch-on point of tank heating at
setpoint value x 0.7
Without LON communication module
LON participant number
LON communication released
Control unit is not error manager
With 5 seconds time delay for fault
With 5 seconds time delay for fault
message
message
Additional information
New coding
Possible change
Address:
Value
62: 0
Circulation pump without run-on
time
62: 1
Run-on time variable from 1 to 15
to
minutes
62: 15
67: 0
Without 3rd DHW set-point
rd
67: 1
Input of a 3
to
temperature; adjustable
67: 95
from 1 to 95˚C / 34 to 203˚F
63: 15
Twice per day
63: 1
Additional function: Once per day
63: 2
Every 2 days
to
to
63: 14
Every 14 days
68: 2
Factor adjustable from 0.2 to 1
to
per 1 increment = 0.1
68: 10
69: 1
Factor adjustable from 0.1 to 0.9
to
per 1 increment = 0.1
69: 9
76: 1
With LON communication module;
recognized immediately
76: 2
With Viessmann 2-wire BUS
communication module; recognized
immediately
77: 2
LON participant number selectable
to
from 1 to 99
77: 99
Please note:
Each number may be assigned
once only.
78: 0
LON communication blocked
79: 1
Control unit is error manager
80: 0
Without time delay
80: 2
Time delay adjustable between
to
10 and 995 seconds;
80:199
1 increment = 5 seconds
set DHW set-point
123