Coding 1; Call Up Coding Level 1; Codings - Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual

Digital boiler control unit
Table of Contents

Advertisement

Coding 1

Call up coding level 1

Codings

Coding as per
Function
factory setting
Address: Value
00: 1
System
type
01: 1
System
type
02: 1
02: 1
Boiler/
Boiler/
burner
burner
03: 0
Boiler/
burner
05: 70
05: 70
Burner
Burner
(mod.)
(mod.)
06: 87
Boiler/
burner
1. Press
and
approx. 2 seconds.
2. Call up the required coding address
with the
press
3. Change the value with the
button; press
4. Press
and
approx. 1 second.
System circuit A1
without domestic hot water
heating
Single-boiler system
Operation with two-stage
Operation with two-stage
burner
burner
Gas-fired operation
Burner curve
Burner curve
Max. limit of boiler water
temperature set to
87°C / 189°F
simultaneously for
or
button;
to confirm.
or
to confirm.
simultaneously for
New coding
Possible change
Address:Value
00: 2
System circuit A1
with domestic hot water heating
01: 2
Multi-boiler system with cascade control
via LON BUS (e.g. Vitotronic 333, Type
MW1)
01: 3
Multi-boiler system with cascade control
via switch contacts (input aVD and aVH)
or 0-10V input module
02: 0
Operation with single-stage burner
02: 2
Operation with modulating burner
03: 1
Oil-fired operation
(coding cannot be reset)
05: 0
Burner curve linear
05: 1
Burner curve not linear:
to
05: 99
Partial output in kW (at g of the
Operating
time of the actuating drive)
Max. output in kW
= Partial output in %
06: 20
Maximum boiler water temperature limit
to
variable between
06:127
20 and 127°C / 68°F and 261°F
Additional information
Access coding level 1.
The first arrow appears in the
display.
Address flashes.
Value flashes.
The value is stored and stops flashing
for approx. 2 seconds. Then the
address flashes and further addresses
can now be selected with the
button.
Exit coding level 1.
x100%
or
115