Connection of External Controls (CT3 only)
Vitocrossal 300 – operation with external modulation controller (continued)
Settings on the control unit
The settings for the fixed high limit and
the other settings are dependent on the
safety equipment installed in
accordance with applicable codes.
Fixed high limit
Adjustable high limit
Coding for the electronic maximum
temperature limiter of Vitotronic 100;
set code 06 to the temperature as
shown or less
Non-condensing boiler
(VD2/VD2A) °C / °F
110 / 230
99 / 210
100 / 212
95 / 203
93 / 200
87 / 188
Single-boiler systems:
Coding "01: 1"
(factory setting)
When a building automation system is
connected, only the connections on
plug aVD are required. The DHW tank
control unit is activated when the DHW
tank temperature sensor is connected.
The boiler water temperature must be
set to the minimum value.
(continued)
Condensing boiler
Condensing boiler
(CT3) °C / °F
(CM2) °C / °F
99 / 210
95 / 203
87 / 188
Multi-boiler systems:
Set coding "01: 3"
When a building automation system
is connected, the connections on
plugs aVD and aVH are required. The
DHW tank temperature and the
load-dependent cascade control must
be controlled through the building
automation system.
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler must
be constantly closed.
Installation
99 / 210
95 / 203
88 / 190
65